InteGREATed Protection




Protection against electromagnetic fields, induced voltage, electric arc.

ABOUT PROTECTIVE SET

The "Electrostatics-1" and "Electrostatics-2" conductive clothing are intended to be worn:

  • during live working (especially bare-hand working) with AC and DC electrical installations, especially with live high voltage power lines;
  • when working on discharged power lines under the electromagnetic influence of the operating AC electrical installations.

Upper layer provides protection against thermal hazards of an electric arc and ignition caused by spark discharge.

Highly conductive band has got electric resistance not more than 0,1 ω/m and can shunt currents up to 35 A without any damage.

Conductive double-sided fabric is a unique material which combines two inseparable surfaces: conductive (steel-silver) and insulating (meta aramid-FR viscose). Such a combination ensures maximum protective features and optimum level of comfort during work. Electric resistance of the conductive surface of the fabric is is not more than 2 ω.

The set provides protection against

  • a harmful impact of the electric field of industrial frequency;
  • electrical discharges while bare-hand working with live-parts;
  • a harmful impact of air ions (including extra heavy air ions - aerosols)
  • a current shock of an induced voltage
  • a thermal hazards of an electric arc.

Fabric system

  • Nomex arc protective FR fabric with oil-and-water repellent treatment (for Electrostatics-2)
  • Highly conductive band
  • Conductive double-sided fabric
Fabric system

Technical information

Electric resistivity of the conductive garment, not more than
1 Ohm
IEC 60895:2002 + corrigendum 2003 modified
Electric resistivity of the conductive gloves, not more than
30 Ohm
IEC 60895:2002 + corrigendum 2003 modified
Electric resistivity of the conductive shoes, not more than
10 kOhm
IEC 60895:2002 + corrigendum 2003 modified
Shield factor at 50 Hz frequency, not less than
70 dB
IEC 60895:2002 + corrigendum 2003 modified
Arc Thermal Performance Value (IEC 61482)
  • Conductive garment
    10 cal/cm2
  • Conductive garment + Nomex upper suit
    22,4 cal/cm2
  • Conductive garment + winter lining + Nomex upper suit
    78 cal/cm2
  • Nomex upper suit
    8 cal/cm2
  • Nomex upper suit with winter lining
    64 cal/cm2

Electrostatics-1

inteGREATed protection
  • A conductive shielding jacket with a hood (a head cover) and a face mesh
  • A conductive shielding bib-and-brace
  • Conductive shielding gloves
  • Conductive shielding boots
  • Two removable equipotential bonding leads with clamps
  • ATPV level - 10 cal/cm2
Electrostatics-1

Electrostatics-2

inteGREATed protection
  • A conductive shielding coverall with a hood (a head cover) and a face mesh
  • Conductive shielding gloves
  • Conductive shielding boots
  • Two removable equipotential bonding leads with clamps
  • ATPV level - 10 cal/cm2
Electrostatics-2

Features of the set

Equipotential bonding leads * between jacket and gloves
Equipotential bonding leads * between jacket and bib-and-brace
Equipotential bonding leads with clamps
Equipotential bonding leads * between bib-and-brace and boots
Equipotential bonding leads between conductive coverall and arc protective upper jacket.
Electrostatics-2 arc protection Electrostatics-2 warm protection

Jacket and bib-and-brace with detachable warm-up undercoat and inner trousers have been developed to be worn at low temperatures under severe climate conditions

Accessories might be ordered separately

Summer and winter conductive gloves
Winter boots made of leather or felt, with fur or in-socks
Summer boots
Electrostatics-2 winter accessories

Cold-proof mittens and leather boots

* All conductive components of the set are connected by equipotential bonding leads